Detailed Operating Instructions of Industrial Chiller
The installation procedures of water
chiller include:
1. During installation, please check
whether the machine is damaged and select a suitable place for installation and
future maintenance. The site for installing the unit must be the floor or
installation pad, with a levelness within 6.4mm, and can bear the operating
weight of the unit.
2. The chiller shall be placed in the
machine room with room temperature of 4.4-43.3 ℃, and there shall be enough space around and above the unit for
daily maintenance.
3. At one end of the unit, a pipe
extraction space for cleaning the condenser tube bundle shall be reserved, and
door holes or other holes at appropriate positions can also be used.
4. Select water pipes with appropriate pipe
diameter, cooling system and cold water system when the unit operates at
maximum power, and connect them correctly.
5. For ordinary applications, the water
flow velocity through the evaporator and condenser is allowed to be between
1.0-3.6m/s.
6. The water flow shall be stable under any
load.
7. All cooling water pipes shall be
designed and installed according to the conventional method. The chilled water
pump shall be located on the inlet pipe of the chiller to ensure the positive
pressure and flow in the unit. When piping, damping pipes shall be set to
ensure proper elasticity, and prevent the water in the evaporator from being
drained when the water pump stops.
8. The pipeline shall be firmly supported
independent of the chiller to avoid stress on the components of the chiller.
9. In order to reduce noise and vibration,
it is better to install vibration isolator on the pipeline.
10. In order to use the chiller
economically and effectively, it is recommended to invite water treatment
experts to analyze the water supply quality of evaporator and condenser. Poor
water quality will cause scale, affect heat transfer, or produce corrosion
precipitation, affect the performance of the unit and increase operation and
maintenance costs.
11. Generally speaking, proper water
treatment and regular cleaning can maintain its good performance.
12. Please install a filter at the inlet of
the water pipe and clean it regularly.
13. After leak test, all nozzle openings
must be treated with rust prevention.
14. In order to facilitate daily
maintenance, the user can take some (or all) of the following measures: the
pressure gauge and stop valve with cock can be installed on the inlet and
outlet pipes of cooling water and chilled water, close to the chiller as far as
possible;
Lifting rails and beams can be erected
above the equipment to facilitate maintenance.
関連推奨品
-
冷暖房温度制御システムにおける温度変化のシミュレーション制御
825工業用冷却・加熱温度制御システムは、製薬・化学工業における反応釜の冷却・加熱工程で使用される温度制御装置です。ルネヤの装置の特徴は?
詳細を見る -
Application area of high temperature refrigeration and cooling control system
871The high-temperature refrigeration and cooling control system is used for supporting glass reactors, rotary evaporators, fermentation tanks, and calorimeters; widely used in petroleum, chemical, metallurgical, biochemical, physics, testing and che...
詳細を見る -
コールドプレートフリーザー[-5~-150度冷凍]の製造業者向け説明書
1099低温コールドプレートフリーザーの様々なメーカーがあります。ガラスリアクター、金属リアクター、バイオリアクターに広く使用され、温度と温度を制御します。 低温コールドプレートフリーザーの使用範囲Mediu...
詳細を見る -
新エネルギー自動車駆動モーター試験システムにおける凍結油の影響
1201新エネルギー車駆動モーター試験システムにおける冷凍機油の危険性は、凝縮温度と凝縮圧力を上昇させ、凝縮器の熱伝達を悪化させる。冷凍機油の油膜は、冷凍機油に混入する油によって生成されるため、冷凍機油の油膜を除去することはできません。
詳細を見る