Explanation of Abnormal Condenser Temperature of Glycol Chiller
In the glycol chiller, the condenser temperature is the saturation temperature when the refrigerant in the condenser condenses under the steam pressure. Once the condenser temperature in the glycol chiller is abnormal, we should analyze the specific causes and find out the solutions.

The condenser temperature of glycol chiller is low
The low temperature of the condenser of the glycol chiller may be due to the large selection of the expansion valve, the failure of the expansion valve or the excessive opening of the expansion valve, which can not achieve the throttling effect. It may also be that the refrigerant charge of the refrigeration system of the glycol chiller is relatively small, which can not reach the specified amount, or the refrigeration system is lack of corresponding refrigerant.
The condenser temperature of glycol chiller is too high
The main reasons for the high temperature of the condenser of the glycol chiller are: the cooling water (or air) flow of the glycol chiller is small, the temperature is too high, or there is air in the refrigeration system of the glycol chiller, which increases the pressure of the condenser of the glycol chiller. Excessive refrigerant charge and insufficient effective condensation area can also lead to high condenser temperature of glycol chiller. If the condenser is out of repair for a long time and the dirt on the heat transfer surface is serious, it can also lead to the increase of condensation pressure, and the existence of scale also has a great impact on the condensation pressure.
Solution to high or low condenser temperature of glycol chiller
The higher or lower condenser temperature of glycol chiller will lead to abnormal compressor exhaust temperature and reduced output coefficient, so as to reduce the refrigeration capacity and increase the power consumption of the compressor. If the exhaust temperature of glycol chiller is too high, the consumption of compressor lubricating oil will be increased and the oil will become thin.
When the exhaust temperature is close to the flash point of compressor oil, some lubricating oil will be carbonized and accumulated at the suction and exhaust valve ports, affecting the tightness of the valve. At this time, it is necessary to reduce the temperature of the cooling medium to reduce the condensation temperature and the condensation pressure, but this is limited by environmental conditions and is difficult to choose artificially.
Increasing the flow of cooling medium can reduce the condensation temperature a little, but it can not unilaterally increase the flow of cooling water or air, because it will increase the power of cooling water pump, fan and motor. It should be comprehensively considered that high exhaust pressure will increase the compression work and reduce the gas transmission coefficient, so as to reduce the refrigeration efficiency. The condenser temperature of glycol chiller is closely related to the smooth operation of glycol chiller, so users should solve it in time if they find that the condenser temperature is abnormal.
関連推奨品
-
環境に優しいコールドプレートフリーザー
950この間、環境保護の監督が急増していることは周知の事実であり、コールドプレート冷凍庫の編集者は、環境保護の意識が広がっていることを皆に伝えている。
詳細を見る -
高温・低温交互湿式ヒートショック試験ボックスの機能説明
914消費者は高温・低温交互湿式ヒートショック試験機の性能に注目する必要がある。LNEYAのテストチャンバーは購買企業のニーズに近い。高温・低温交互ヒートショック試験機...
詳細を見る -
低温チラーの主な機能
1026国内の産業市場では、低温のスリラーは異なった産業生産に適した労働環境を提供できる非常に重要な生産の補助装置です。コンデンサーは低温のスリラーの主要な部分の1つである。
詳細を見る -
Maintenance method of minus 17 ° C ultra-low temperature refrigerator
1038After the long-term use of the ultra-low temperature refrigerator of minus 17 °C, it is necessary to carry out certain maintenance work. If the user does not know how to carry out the maintenance work, you can contact the manufacturer to obtain th...
詳細を見る