冷却水循環装置 駅全体を検索

精密空調機・外気処理空調機・恒温恒湿

は、周囲の温度と湿度を精密に制御するための空調装置で、従来の水冷式とマイクロ空冷式があります。

精密温湿度コントロールユニット(水冷式)

Model LMW-01BS LMWX-01BS LMW-03BT LMWX-03BT
Rated Airflow m3/min 0.7~1.0 2.0~4.0
Adjustable Temperature & Humidity Range  ℃/ %RH 21~26 21~26;45%RH~60%RH 21~26 21~26;45%RH~60%RH
Temperature/Humidity Control Accuracy ℃/ %RH ±0.1 ±0.1;±1.0%RH ±0.1 ±0.1;±1.0%RH
Maximum Cooling Capacity(50/60Hz) KW 0.2/0.25 0.37/0.45 1.3 1.3
Reheating Capacity(50/60Hz) KW 0.1/0.13 0.4 0.5 0.7
Maximum Humidification Capacity Kg/h / 0.8 / 2.3
Humidification Water Supply Temperature Range / 10~40 / 10~40
Humidification Makeup Water Pipe Connection / / Rc1/2 / Rc1/2
Humidification Makeup Water Pressure bar / 0.3~2 / 0.3~2
Water Quality Requirement / /

*Conductivity125~1250μs/cm     

*Water hardness not exceeding 40°f        

*Free of organic compounds

/

*Conductivity 125~1250μs/cm     

*Water hardness not exceeding 40°f         

*Free of organic compounds

Maximum External Static Pressure of Supply Air Pa 120/130 120/160 110/150 110/150
Supply Air Outlet Connection Diameter mm φ75 φ100 φ100 φ100
Equipment Ambient Temperature ℃/ %RH 20~26;40%RH~60%RH ①
Ambient Temperature Accuracy Range ℃/ %RH ±1;±5%RH
Power Supply V/Hz 1~220v±10%; 50/60Hz±5Hz   3~380v±15%; 50Hz±5Hz  ④ 
Unit Rated Input Power KW 0.32/0.34 1.2/1.2 0.75  ⑤ 2.7 ⑤
Max Operating Current of Unit A 1.7/1.82  6.4/6.4  1.35 4.8
Unit Noise Level(50/60Hz) dB(A) 54/56 58/60 65 66
Max Input Power of Unit KWA 0.34/0.38  1.5/1.5  1.4 4
Refrigerant/Charge Quantity Kg R134A/0.13 R407C/0.3 R410A/0.4 R410A/0.48
Unit N.W Kg 32 69 95 135
Unit G.W Kg 40 85 110 150
Unit Overall Dimensions(L*B*H) mm 500*412*346 630*390*765  590*480*1070 680*520*1350
Unit Packaging Dimensions (L*B*H) mm 600*500*400 750*500*850 700*600*1200 780*650*1400

備考:

1、温湿度制御範囲は、必ずしも実際の制御可能範囲を示すものではありません。実際の制御可能範囲は、入口温度・湿度、およびプロセス風量に依存します。使用環境に応じてプロセス風量を設定してください。
2、M01/02シリーズの場合、入口温度・湿度が安定している状態では、コントローラに表示される精度は、出口1点のみに適用され、最大定格風量で運転した場合の精度です。
M03シリーズの場合、定格風量(3 m³/min)で運転すると、コンプレッサオイルの逆流により、起動後約2分間は一時的に温度が変動します。また、目標湿度が高い場合、加湿水供給のタイミングによっては、前述の精度を維持できない場合があります。このような場合は、給水に関するパラメータを調整することで、変動幅を低減できます。
3、最大定格風量で運転した場合、給気ファン出口側の空気出口における静圧は一定です。
4、電圧降下を防ぐため、本製品は専用コンセントに差し込んでください。三相電源電圧の位相不平衡は±3%未満にしてください。
5、規定範囲内で最大動作電流で運転する場合。
6、冷却水の水質要件:「工業用循環冷却水処理設計規格」GB50050-95の基準値を下回らないでください。注:40°FはCaCO₃濃度400ppmに相当します。7、高さは出口端を含みます。記載されている値は、規定の最大加湿レベルで運転した場合のものです。詳細は取扱説明書をご参照ください。

備考: 給気ダクトは断熱する必要があり、現場での設置ではパイプラインの長さを可能な限り短くする必要があります (最大長は 3 m を超えてはなりません)。

精密温湿度コントロールユニット(空冷式)

Product Model LW-0090-BW01 LWX-0090-BW01 LW-0100-BW01 LWX-0100-BW01
Rated Airflow m3/h 8000~9000  9000~10000  
Adjustable Temperature & Humidity Range  ℃/ %RH 22~23;45%RH 22~23;45%RH 22~23 22~23;45%RH~70%RH
Temp./Humidity Control Accuracy    ℃/ %RH ±0.1 ±0.1;±1%RH ±0.1 ±0.1;±1.0%RH
Max Cooling Capacity KW 20kw @25℃ 16kw @26℃
Max Humidification Capacity Kg/h / 5 / 2.3
Outdoor Air Ratio  ②   20% 20% / /
Equipment Outdoor Air Temp & Humidity Range ℃/ %RH 23±2;;40%~60%±2%RH 25; 50%RH
Equipment Return Air Temp & Humidity Range ℃/ %RH 23±0.1;45%RH ±2%RH /
Max External Static Pressure of Supply Air Pa 300~400 0~200
Supply Air Outlet Connection Diameter mm φ500 φ500
Humidification Water Supply Temp Range / 10~40 / 10~40
Humidification Makeup Water Pipe Connection / / Rc1/2 / Rc1/2
Humidification Makeup Water Pressure bar / 1~4 / 1~4
Water Quality Requirement / /

*Conductivity75~1250μs/cm      *Water hardness not exceeding 40°f         

*Free of organic compounds

/

*Conductivity 75~1250μs/cm      *Water hardness not exceeding 40°f        

*Free of organic compounds

Cooling Water Temperature 18~22 18~22
Cooling Water Connection   G1″ G1″
Power Supply V/Hz 3~380v±10%; 50Hz±5Hz  Three-phase five-wire system
Unit Rated Input Power KW 12.5 12.5 4 4
Maximum Operating Current of Unit A 23 23 7 7
Unit Noise Level dB(A) ≤80 ≤75
Maximum Input Power of Unit KWA 15 8
Refrigerant/Charge Quantity Kg R410A/4 R410A/4
Safety Protection Functions   Power overvoltage and undervoltage protection; phase reversal and loss protection; motor overheat and overload protection; compressor discharge temperature overheat protection; system high pressure protection; system low pressure protection; temperature module fault protection; adjustable over-temperature protection; fan motor overheat protection, etc.
Unit N.W Kg 750 800 650 680
Unit G.W Kg 800 850 700 750
Unit Overall Dimensions (L*B*H) mm 2130*1000*2000 1200*1200*1950 
Unit Packaging Dimensions(L*B*H) mm 2300*1150*2100 1350*1350*2050

備考:

1、温度・湿度制御は異なる設定温度に対応できるだけでなく、一定の動作温度・湿度で安定運転することも可能です。
2、本機は実際の状況に応じて外気量を調整し、HVACの外気要件を満たすことができます。
3、精密恒温恒湿ユニットの外気および還気の温度・湿度範囲。
4、最大定格処理風量で運転時、給気ファン出口側の空気出口における静圧は一定です。端末にFFU(ファンフィルターユニット)が装備されているかどうかに応じて調整することもできます。5、440°FはCaCO₃濃度400ppmに相当します。
6、冷却水の水質要件:工業用循環冷却水処理設計規格GB50050-95以上。
7、給気ダクトは断熱材で覆われている必要があり、現場設置時には配管長を可能な限り短くする必要があります。詳細は取扱説明書をご参照ください。

高精度と高効率を確保するための鍵

環境空気温度制御ユニットの適用シナリオ


半導体、液晶、太陽光パネルなどの製造設備で使用される装置、製造工程、検査工程、空間には高精度で安定した空気処理が求められます。

LQ -110℃~-40℃
窒素フリーザー

ガス量15m³/h〜100m³/h 
サーキットブレーカ10A〜25A 
最低温度-40℃/-75℃/-110

AES -120℃~225℃
温度強制システム/熱風機

温度精度±0.1℃  
ガス体積処理能力10m³/h〜30m³/h 5bar〜7.6bar  
温度上昇・下降速度<10秒

AET -75℃~250℃
温度試験装置

温度範囲:ガス出口±0.1℃リモートプロセス±0.5℃
空気処理能力22m³/h~95m³/h
昇温降下速度<10秒

AI -105℃~125℃
空気循環のスリラー

暖房力3.5KW
冷却力1KW~3.5KW
温度精度±0.05℃

DRシリーズ
半導体ガス乾燥装置

圧力範囲0.65~1.0Mpa
露点温度-70℃
ガス処理能力425L/分~1750L/分

なぜLNEYAを選ぶのか?

❯15年以上の設計・生産経験 (ワンストップサービス )
❯短納期
❯ 強力なアフターサービスと技術サポート
❯高精度で再現性の高い温度制御
❯ 130件の特許を保有

ワールドワイドサービス

30,000以上の顧客にサービスを提供。20カ国以上に輸出

認定特許

CE認定、SGS認定、ISO認定

アフターサービス

包括的な技術トレーニングを提供します。年中無休のソリューション提供

プロフェッショナルチーム

2010年に設立され、15年の業界経験を有し、技術者が全従業員数の20%を占める

品質管理

外観検査。性能テスト。電気安全テスト

*
*
*