完全に密閉された冷暖房サーモスタットの冷媒アラーム不足の解決策

What should I do if the fully enclosed heating and cooling thermostat alarms for lack of refrigerant? I believe that many customers will encounter this problem when they use it. In fact, this is relatively simple. As long as we know the principle of the lack of refrigerant alarm, it can be solved very well. Today I will share two points with you so that everyone will encounter this problem. It can be solved very quickly.


When we encounter a refrigerant shortage alarm in a fully enclosed heating and cooling thermostat, the first thing we have to do is to check to see if the liquid level on the expansion tank of the fully enclosed heating and cooling thermostat is at the normal level, if it expands at this time The liquid level of the fuel tank is lower than the low level, then this alarm is caused by the lack of oil in the system. What we need to do is to add new heat transfer oil in time until the system has a stable pressure and the liquid level of the expansion tank is at the normal level. It can be solved.

There is another situation that will also cause the fully enclosed heating and cooling thermostat to alarm for lack of refrigerant. That is, an alarm occurs after a period of use. At this time, we also need to check the liquid level of the expansion tank. If the heat transfer oil is lower than the low level, there must be a leak in the pipeline, which needs to be found and repaired in time. If it is not the leakage problem, then Most of it should be that the liquid level float switch of the expansion oil tank touches the wall of the expansion oil tank, causing the liquid level switch to not work normally. At this time, we need to remove the liquid level switch and re-reinforce it. The main reason for this situation may be due to The fully enclosed heating and cooling thermostat is caused by slight vibration during use.

The above are two solutions for the lack of refrigerant alarm. The alarm is a fully enclosed heating and cooling thermostat’s built-in protection, mainly to prevent the heating tube from burning dry, so when we encounter this problem, we can solve it in most cases according to the two methods shared by the editor. If it is solved No way to contact LNEYA after-sales technical support.

前の記事 次だ:

関連推奨品

  • 熱油二次循環システムの安全知識

    1123

    熱油二次循環システムは、温度制御のための様々な機器や装置が装備されている。市場調査、入念な研究、温度制御製品の生産の後、使用する際には、注意を払う必要があります...

    詳細を見る
  • 500 liter reactor cooler selection instructions

    1044

    The 500 liter reactor chiller is used more in the pharmaceutical industry. Therefore, the user needs to select a regular manufacturer when selecting, and at the same time, understand the features and configuration. For the selection of 500 liter r...

    詳細を見る
  • 空冷式スクリュー冷凍機の3つの一般的な故障

    1317

    1.通信障害:コンピュータ・コントローラは、電気通信回線とトータル・インターフェース・ボードによって様々なモジュールを制御しているため、通信障害の主な原因は、通信回線の接触不良や断線、特にインターフェース・オキシダ...

    詳細を見る