ステンレス鋼製極低温冷凍機の高圧破損
At the high speed of the stainless steel cryogenic refrigerator compressor, the temperature rises and the compressor generates high air pressure, which causes the high voltage protection relay to operate. The discharge pressure of the compressor reflects the condensing pressure. The normal value should be 1.3~1. 7MPa, and the protection value of the Wuxi Guanya stainless steel cryogenic refrigerator is set to 2.1MPa. Then, if it is a long-term work, the compressor pressure is too high, which will lead to excessive operating current of the compressor, easy to burn the motor, and easily cause damage to the valve port of the compressor exhaust port.
The equipment condenser is dirty or clogged. The cold water is generally tap water. It is easy to scale when it is above 30 °C, and since the cooling tower is open, it is directly exposed to the air, and dust foreign matter can easily enter the system, causing the condenser to clog. The unit should be backwashed regularly and chemically cleaned if necessary.
The stainless steel cryogenic refrigerator has insufficient cooling water flow and cannot reach the predetermined water flow. The main performance is that the pressure difference between the inlet and outlet water of the unit becomes smaller and the temperature difference becomes larger. The reason for the insufficient flow is: the system is short of water or air. The solution is to install an exhaust valve at the high point of the pipeline to exhaust; the pipeline filter is blocked or too fine, and the water permeability is limited. The appropriate filter should be selected and periodically. Clean the filter.
The cooling water temperature of the equipment is high and the condensation effect is poor. The rated working condition of the cooling water required by the unit is 28~35°C. The water temperature is high and the heat dissipation is bad, which will inevitably lead to high condensation pressure. This phenomenon often occurs in summer.

So what are the reasons for the high water temperature of stainless steel cryogenic refrigerators?
Stainless steel cryogenic refrigerator cooling tower failure, such as the fan is not open or even reverse, the water distributor does not turn, the performance of the cooling water is high, and rapid rise; 2. The temperature is high, the water is short, and the amount of water that can be recycled is small. The stainless steel cryogenic refrigerator has too much refrigerant and is mixed with air, nitrogen and other non-condensable gases. This situation usually occurs after maintenance, and the vacuum is not complete. Can only be drained, re-vacuum, refill the refrigerant. False alarm caused by electrical failure of stainless steel cryogenic refrigerator. Due to the moisture, poor contact or damage of the high voltage protection relay, the unit electronic board is damp or damaged, and the communication failure causes a false alarm. This kind of false fault, often the HP fault indicator on the electronic board is not bright or slightly bright, the manual reset of the high voltage protection relay is invalid, and the computer displays “automatic disappearance”. The compressor running current is normal, and the suction and exhaust pressure is also normal.
Therefore, the equipment needs to solve the fault in time, and it is necessary to perform regular maintenance and maintenance work. If there are other technical problems, you can contact the stainless steel cryogenic refrigerator Wuxi Guanya LNEYA professional manufacturer.
関連推奨品
-
Noise description of common faults in high and low temperature integrated equipment
1213High-low temperature integrated machine equipment may cause malfunction due to improper operation, then how to deal with noise failure of the equipment, and then analyze the noise too high. The suction of high and low temperature integrated equipm...
詳細を見る -
483蒸留CBD抽出のための夢の機器との出会い
1249CBDを蒸留するための装置が必要な場合、その装置の機能やデザインは様々であるため、選択肢を精査する必要があります。CBD蒸留液を製造する機器を使用する場合、CBD蒸留液を製造するメーカーが製造したシステムを求めたいものです。
詳細を見る -
Step-by-step test box brand advantage description
1252The walk-in test box is developed and produced by LNEYA. It is specialized in pharmaceutical production technology and provides customers with various models of brands. Next, we will introduce the next step-in test box. Welcome to refer to and lea...
詳細を見る -
高温密閉型防爆型工業用冷凍機における冷凍要素の影響
1111高温・低温の密閉型防爆工業用冷凍機が故障の原因になっていないかチェックする。選定は正確でなければならない。機種がずれていると、必要な冷凍効果も得られない。それは...
詳細を見る