Multi-stage refrigeration system centrifugal compressor repair instructions
After the centrifugal compressor of the cascade refrigeration system is disassembled, the dimensions of each journal (cooperating with the impeller, bearing, coupling, etc.) are measured with an outer diameter micrometer to calculate the roundness and cylindricity deviation. The value should be Within the allowable range. When the tolerance is large, check if the straightness deviation of the spindle is too large. Place the spindle in the casing or place it on the top of the lathe so that the spindle is in a free state. Use a dial gauge to measure the radial runout of the spindle journal.
The centrifugal compressor of the cascade refrigeration system is divided into 4-8 equal parts, and the rotor is driven according to the direction of rotation of the rotor. The large value of the dial gauge swing is the radial circle runout value. At the same time, the straightness deviation of the main shaft is measured at the appropriate position of the main shaft with two dial gauges, and the radial runout value should be no more than 0.01mm. If the over-standard is too large, the main shaft should be replaced.
Check the surface of the journal of the centrifugal compressor of the cascade refrigeration system for scratches, grooves, scratches, grinding points, etc. If necessary, perform flaw detection. Small defects can be scraped and polished by hand; large defects It can be repaired by surfacing, electroplating, spraying, etc., and then ground and polished. When the flaw detection reveals cracks or serious defects, it is generally not repaired and replaced.
At the same time, the end face runout of the centrifugal compressor impeller of the cascade refrigeration system should be measured, and the value should be within the allowable range. If the value of the end face jump exceeds the allowable range value, when the over-standard is small, the repair is generally not performed. When the value is large, the assembly relationship between the impeller and the main shaft can be adjusted by the method of adding the gasket. The impeller should be dynamically balanced and statically balanced after the overhaul. test.

The parts and fittings of the centrifugal compressor of the cascade refrigeration system have the specified technical standards and requirements for use. In the absence of reliable basis, it is necessary to strictly abide by these standards and never lower the standard.
The cascade refrigeration system should have a fixed maintenance and repair plan, carefully learn the correct understanding and use of equipment requirements by the user, and timely cooperate with the on-site user for regular maintenance.
関連推奨品
-
What type of temperature control system is required for smear preparation in the pharmaceutical industry?
885In the pharmaceutical industry, negative pressure drying and smear preparation have specific requirements for temperature control, and usually require precise and adjustable temperature control devices to ensure product quality and process sta...
詳細を見る -
Pharmaceutical industry reactor supporting equipment high and low temperature thermostat
928The high and low temperature thermostat is a temperature control device used in the pharmaceutical industry to heat the reactor for different time periods. It is simple and convenient to operate, and can quickly improve the temperature rise and fa...
詳細を見る -
塩水噴霧環境チャンバーの一般的な不具合
1056塩水噴霧環境槽の一般的な故障に対処する際、企業ユーザーはしばしば途方に暮れる。そのため、塩水噴霧環境室のメーカーである無錫LNEYA社は、塩水噴霧環境室に関連する一般的な故障を特別に再編成し、塩水噴霧環境室における一般的な故障を解決するための方法を提供する。
詳細を見る -
チラーの断熱性はどの程度重要ですか?
1297回答冷凍機の場合、高温で運転すると工業用冷凍機内の冷気が大量に失われる可能性があります。使用環境の密閉効果後、タイムリーで効果的な保温を行うことで、工業用冷凍機の運転...
詳細を見る