空冷式スクリュー冷凍機の3つの一般的な故障
空冷式スクリュー冷凍機の3つの一般的な故障
1. Communication Failure:
Computer controller controls various modules by telecommunication lines and total interface board, so the main cause of communication failure is poor contact or break of communication lines, especially the interface oxidation and damp of the interface. Also, the failure of unit electronic board or total interface board, incorrect choice of address dial code switch and power failure can cause the communication failure.
2. Low Voltage Failure:
The low suction pressure of the compressor results in low pressure protection relay action. The suction pressure of the compressor reflects the evaporation pressure, whose the normal value should be 0.4~ 0.6mpa, and the protection value is set to 0.2mpa. Low suction pressure causes low return air volume and insufficient cooling capacity, resulting in waste of electrical energy and the heat dissipation of the motor of gas cooled compressor which is easy to damage the motor.
3. High Voltage Failure:
High exhaust pressure of compressor results in high voltage protection relay action. The compressor exhaust pressure reflects condensation pressure whose normal value should be 1.4~ 1.6mpa, and the protection value is set to 2.0mpa. If the pressure is too high for a long time, it will cause too large of the current of compressor, which is easy to burn the motor and damage the compressor exhaust valve disc.
関連推奨品
-
Design of chip test circuit for fluid temperature control device
1237With the continuous development of the domestic chip industry, LNEYA fluid temperature control devices continue to be applied. To this end, the circuit design for the fluid temperature control device chip test, the fluid temperature control device...
詳細を見る -
Large industrial refrigerator evaporator operation instructions
1186In the operation process of Wuxi Guanya LNEYA large industrial refrigerator, due to the large number of parts and complex, we need to understand the operation of the components in large industrial refrigerators. The evaporator is one of the main c...
詳細を見る -
Small environmental test chamber compressor should pay attention after maintenance
1090In the centrifugal small-scale environmental test chamber, the suction recovery device is generally an independent system, and if necessary, the pipeline connected to the condenser and the evaporator can be closed for separate maintenance. After r...
詳細を見る -
Guanya Refrigeration, a Brand Enterprise of Refrigeration Chillers, Leads the New Development
963Guanya Refrigeration Technology Co., Ltd. (hereinafter referred to as the "Guanya Refrigeration") brand "LNEYA" in English, specialized in refrigeration equipment, cryo chillers, ultra-low temperature freezer, refrigeration, and heating temperatur...
詳細を見る