低温冷凍バスでよくあるデバッグの問題とは?

When the low-temperature cooling bath is in debugging, if the local cooling effect is not good, the system may be blocked by foreign matter or the system design is unreasonable and cannot be adjusted normally. At this time, LNEYA removes foreign matter and thoroughly cleans it to adjust the slope of the pipeline.

When debugging, it is found that the vibration and noise of the pump are large when it is running. It may be that the axial and radial deviation of the coupling is large. It may be that the pump flange is too large and the anchor bolts are unevenly stressed. It is the natural vibration frequency of the pump and the pipeline that cause resonance. At this time, the axial and radial deviation of the coupling are adjusted quickly. Adjust the natural vibration frequency between the pump and the pipe, install the relevant soft joint parts, replace the flange and make the anchor bolts evenly.

During commissioning, it was found that the cooling capacity could not reach the required fixed value. It may be that the cooling tower water temperature did not reach the specified cooling parameter, or the pump output was insufficient, or the condenser isolation gasket was misplaced and could not be cooled, or the pipeline in the condenser was blocked. Repair the cooling tower to meet the water temperature and water requirements, remove foreign matter in the pipeline, and check if the condenser isolation gasket is misaligned.

If the exhaust pressure is too high, it is necessary to pay attention to whether the cooling water is insufficient, whether the condensation in the condenser heat transfer tube is serious, whether the cooling water temperature is too high, whether there is too much air in the system, check the cause, repair the cooling tower, and heat transfer of the condenser. The tube is cleaned to remove air from the system.

If severe frost formation is found, check if the return air filter is clogged, if the exhaust air volume is loose after the fan belt is loose, and if the return air valve is too small, it is recommended to clean the return air filter and adjust the fan belt. Adjust the size of the return air valve.

Common faults encountered in the commissioning of these low-temperature refrigeration baths, we try to check them before debugging, try to avoid these faults.

前の記事 次だ:

関連推奨品

  • 冷熱機器メーカーのLNEYAです。

    1270

    LNEYA冷凍機メーカーは、冷凍および加熱温度制御システム、超低温冷凍庫、新エネルギー自動車部品試験システム、および加熱サイクルシステムのTOTH研究開発、生産、販売に取り組んでいます。...

    詳細を見る
  • LNEYAチラーの原理

    1121

    産業用冷凍機は、射出成形、工具・型抜き、食品・飲料、化学、レーザー、工作機械、半導体など、さまざまな用途の製品や機械を冷却するために一般的に使用されています。ほとんどの...

    詳細を見る
  • 工業用高温・低温冷却システムの作動特性

    988

    工業用高温低温冷却システムは、主に温度、圧力、流量、液面、湿度、pH値などの監視と制御に使用されます。高い制御精度、高い信頼性、高い信頼性、高い信頼性、高い信頼性、高い信頼性、高い信頼性、高い信頼性、高い信頼性。

    詳細を見る