Maintenance Method Of Ultra Low Temp Chiller Refrigeration System
について ultra low temp chiller refers to the refrigeration unit whose chilled water temperature reaches below minus 35℃. The unit adopts two-stage compression refrigeration, and the combination of the scroll compressor and the piston compressor is used to manufacture a freezing source of minus 35℃ or even minus 60 ℃, to meet the requirements of the production process, to ensure the normal and smooth production.
Firstly, the leak detection of ultra low temp chiller system.
1. The refrigerant side of the unit has undergone a strict leak detection process during the factory and commissioning process.
2. After the unit is running, check the high-pressure part with the leak detector to ensure the tightness of all connections.
3. If a leak is found, it should be disposed of immediately. In general, the connection of the nano or flange bolts can be used to eliminate the leaks, but there is also the possibility that the refrigerant be recovered and then the leaks must be treated. Such as the leakage of welded joints.
Second, the system’s pressure leak detection.
The standard pressure leak detection steps for ultra low temp chillers are as follows:
1. Fill a small amount of R-22 gas to a system pressure of 2PSIG.
2. Fill the system with nitrogen to 25~50 PSIG. Make sure the pressure reaches all parts of the system. The oil valve can be opened slightly, and the leak detector is used to check whether there is refrigerant.
3. Check each joint and weld, and try to be careful and spend as much time as possible. The leak detection equipment used must be sensitive and reliable.
4. Open the top bleed valve of the evaporator and condenser to confirm that no refrigerant has been detected. If refrigerant is found, the end cap should be removed to remove the internal leak.
5. Confirm that the system is completely sealed, and the gas is released from the system at an appropriate flow rate from the filling valve to perform a certain purging action.
Thirdly, vacuuming and drying of ultra-low temperature chiller system.
1. Connect the high efficiency vacuum pump and the mercury vacuum gauge in series with the filling valve of the system.
2. Open all valves of the system that connect the valve, the suction valve and the vacuum gauge. Confirm that all valves that pass through the atmosphere are closed.
3. Start the vacuum pump and pump the vacuum to 5mmHg.
4. If there are conditions, 50oC of hot water can be introduced into the system to accelerate the evaporation of the system’s memory and improve the dryness.
関連推奨品
-
Beginning with Refrigeration, Heating and Temperature Control System Product Diversification Develo
1013Wuxi Guanya Refrigeration technology co., ltd was founded in 2006. It set up a refrigeration and heating equipment studio. In 2007, it launched the first generation refrigeration and heating cycle, registered the trademark "LNEYA". In 2008, it lau...
詳細を見る -
Application of jacketed reactor cooling and heating circulator in chemical reactions
1034jacketed reactor cooling and heating system application
詳細を見る -
新エネルギー自動車用バッテリーの電力試験システムとは?
941The LNEYA power battery system is tested for battery testing of new energy vehicles, but modern new energy vehicles have many types of batteries. So what are the characteristics? The ternary lithium battery refers to a lithium battery in which the...
詳細を見る -
LNEYA試験室用循環式冷凍機はどのような機器に使用できますか?
876実験室用循環式冷凍機は、科学研究や工業生産において幅広い用途があり、様々な実験や機器に正確な温度制御を提供します。以下は、一般的なシナリオです。
詳細を見る